MP series modular UPS from 20 ~ 720 kVA

Product profile

MP series is a three-phase UPS, which adopts modular design and N+X parallel redundancy technology. Its product capacity covers all power sections from 20/30/40/50/60kVA to 200/300/400/600/720kVA, facilitating flexible onfiguration and gradual investment by users. This series of UPS can completely solve all power supply problems, such as power failure, high voltage and low voltage of mains power, instantaneous voltage drop, amplitude reduction oscillation, high voltage pulse, voltage fluctuation, surge voltage, harmonic distortion, clutter interference, frequency fluctuation and other power supply problems.


Basic Features

This product covers a wide range, from computer equipment to communication systems and automatic equipment.


1. High-reliability design?

Ultra-wide input voltage range 138~485 Vac (phase voltage 80~280 Vac), use above 305 Vac


2. Energy saving and green environmental protection

High input PF value, up to 0.99 , three-level topology structure, the whole machine efficiency is up to 96.5%


3. Parallel redundancy function

Direct parallel machine, 6 parallel ,support parallel machine sharing battery pack


4. Flexible battery configuration scheme

30~50 optional · single large capacity charging power, to meet the backup requirements of long delay


5. Super-loading capacity

Output power factor 0.9 / 1, can take 100% unbalanced load,load adaptability, can be near full load of pure perceptual load and capacitive load


6. Compatible with generator operation

Power Walk In Function, reduce the impact current of the system start, reduce the demand of the generator capacity of the parallel system


7. The LBS synchronization function?

With LBS synchronization function, to achieve two sets of independent UPS system synchronization, improve the reliability of the system


8. Intelligent management function?

Support RS485, SNMP, dry contact and CAN interface


Technical Specifications


Model(maximum capacity)

MP200kVA/MP300kVA/MP400kVA/MP500kVA/MP600kVA/MP720kVA

Capacity

UPS ? cabinet

20-200kVA/30-300kVA/40-400kVA/50-600kVA/60-720kVA

Module

20kVA/30kVA/40kVA/50kVA/60kVA

Main road input

Input mode

Three-phase, four-wire + grounding

Rated voltage

380/400V/415VAC

Voltage range

138-485VAC; 305-485VAC (not decreased); 138-305 VAC)

Frequency range

40~70Hz

Power factor

0.99

Input current harmonics

3% ? (100% linear load)

Bypass input

Input voltage

380/400/415VAC

Bypass range

Upper bypass protection voltage: +25% (optional?+5%, +10%, +20%)

Lower bypass protection voltage limit: -45% (optional -20%, -30%)

The wiring system

Three phase five line

Bypass ? synchronization tracking range (Hz)

50/60±10%

Power?Walking?In

Support

Bypass anti-port

Support

Generator access

Support

Output

Rated voltage

380/400/415VAC±1%

Power factor

0.9/1.0

Voltage accuracy

±1%

Output ? frequency

Main ? mode

Synchronized with input; the output frequency is 50/60 (±0.2% Hz when the mainmax exceeds ±10% (±1%, ±2%, ±4%, ±5% are set)

Battery ? mode

50/60(±0.1%)Hz

The load peak ratio

3:1

Switching period

Municipal mode to bypass mode: 0ms (tracking);?

municipal mode to battery mode: 0ms

Overload capacity

Load≤110%, 60min, 125%, maintained for 10min, and 150% for 1min

Output voltage distortion

≤2% linear load

With<4% nonlinear load

Efficiency

Normal mode

≥96.5%

Communication interface

UPS cabinet

RS232, RS485,2 Intelligent Slot (smart card slots), dry contact

Battery

Battery voltage

±180~±300Vdc (optional in 30~50 sections)

Work environment

Working temperature

-10℃~45°℃

Relative humidity

0~95% ? with no condensation

Storage temperature

-20℃~65°℃

Altitude

<1500m

Noise (DB)

<70 (at 1 m)

Physical ? characteristics

20/30/40kVA
? 3 Module cabinet

20/30/40kVA
? 5/6 Module cabinet

20/30/40kVA
? 10 Module cabinet

50/60kVA
? 10/12 module cabinet

Size ? W×D×
? H(mm)

UPS ? system cabinet

600×840×1400

600×840×1400

600×1100×2000

1200×850×2000

Module

440×580×13086

440×620×130

Weight ? (Kg)

UPS ? system cabinet

157

169

306245

435/510

Module

3221

33

Executive standards

Executive standards

CE, EN/EC?62040-2,EN/IEC?62040-1-1,YD/T2165-2017

The above parameters may be changed, please meet the international EMC safety regulations